15
Circuit breakers interrupt electrical current to stop power flow both for switching
operations and during fault conditions.
·
Molded case circuit breakers are usually located in low voltage distribution panels
and in control boards. These are typically 120-volts alternating current (Vac),
125-volts direct current (Vdc), 240-Vac, and 480-Vac breakers for control,
protection, and auxiliary power. Molded case breakers in panel boards should not
be loaded more than 80 percent of rating per NFPA 70B, 11-2.
·
Low voltage air breakers are usually located in motor starter cabinets, motor
control centers, station service switchgear, or similar enclosures. These are
typically 480 Vac for auxiliary power.
·
Medium voltage circuit breakers are generally located in station-service metal
clad switchgear or in separate enclosures as unit breakers. Examples are
4160-Vac station service, 11.95-kV and 13.8-kV unit breakers. These breakers
may be air, air blast, vacuum, or SF6.
·
High voltage circuit breakers are located in separate breaker enclosures, either
indoors or outdoors. These are oil, air-blast, or SF6 breakers. Examples are
115-kV and 230-kV breakers located in the switchyard.
·
Extra high voltage (EHV) circuit breakers are not addressed in this FIST volume.
Reference the manufacturer's instruction books.
Most breaker maintenance (except infrared scanning) must be performed with
equipment de-energized.
Maintenance or Test
Recommended Interval
Reference
Review equipment ratings
5 years
NERC Planning Standard
Visual inspection
3-6 years
NFPA 70B, 11-8 and
Appendix H
Mechanical operation
by hand
3-6 years
NFPA 70B, 11-8 and
Appendix H
Infrared scan
Annually
NFPA 70B 18-17