EZ Maintenance CMMS Software Img



background image
11
4.3 Maintenance Schedule ­ Valve Regulated, Lead Acid (Gel Cel) Batteries
Maintenance or Test
Recommended Interval
Reference
Visual inspection
Monthly
FIST Volume 3-6, Table 3
Battery float voltage
Shift, monthly
FIST Volume 3-6, Table 3
Cell float voltage
Monthly, semi-annually
FIST Vol 3-6, Table 3
Temperature
Quarterly
FIST Volume 3-6, Table 3
Connection resistance
Quarterly (25 percent)
Annually (100 percent)
FIST Volume 3-6, Table 3
Internal resistance
Quarterly
FIST Volume 3-6, Table 3
Capacity testing
Annually and semi-annually If
capacity test less than
90 percent
FIST Volume 3-6, Table 3
IEEE 1188-1996
Safety equipment inspection
Monthly
FIST Volume 3-6, Table 3
IEEE 1188-1996
Infrared scan
Annually
NFPA 70B 18-17
4.4 Maintenance Schedule ­ Vented Nickel Cadmium Batteries
Maintenance or Test
Recommended Interval
Reference
Visual inspection
Monthly, annually
FIST Volume 3-6,
Table 4
Battery float voltage
Shift, monthly, quarterly,
semi-annually
FIST Volume 3-6,
Table 4
Cell float voltage
Quarterly
FIST Volume 3-6,
Table 4
Temperature
Quarterly (pilot cell)
FIST Vol 3-6, Table 4
Intercell connection retorque
Annually
FIST Volume 3-6,
Table 4
Capacity testing
5-year, annually if capacity less than
90 percent
FIST Volume 3-6,
Table 4
IEEE 1106-1995
Safety equipment inspection
Monthly
FIST Volume 3-6,
Table 4
IEEE 1106-1995
Infrared scan
Annually
NFPA 70B 18-17
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance

This Information is Reprinted From UNITED STATES DEPARTMENT OF THE INTERIOR BUREAU OF RECLAMATION