EZ Maintenance CMMS Software Img



background image
9
2.2 Maintenance Schedule for Annunciators
Maintenance or Test
Recommended Interval
Operational test
Each shift ­ staffed plants
Each visit ­ unstaffed plants
Functional test
Annually
3. ARRESTERS
3.1 General
Lightning or surge arresters provide protection for important equipment from high-
energy surges. These arresters are static devices which require fairly infrequent
maintenance. Most maintenance must take place while the associated circuit is
de-energized. However, crucial visual inspections and infrared scans can take place
while energized.
3.2 Maintenance Schedule for Arresters
Maintenance or Test
Recommended Interval
Reference
Review equipment rating
5 years
North American Electric Reliability
Council (NERC) Planning
Standard
Visual inspection with
binoculars
Quarterly to semi-annually
Reclamation Recommended
Practice
Clean porcelain and check
connections
3-6 years
Ambient dependent
Manufacturer's Instruction Books
Doble test (power fre-
quency dielectric loss, direct
current [DC] insulation
resistance, power factor)
3-6 years
Ambient dependent
Doble Test Data Reference Book,
NFPA 70B
Infrared scan
Annually
NFPA 70B 18-17
CMMS Fleet Maintenance Software for Fleet, Vehicle, & Equipment Maintenance

This Information is Reprinted From UNITED STATES DEPARTMENT OF THE INTERIOR BUREAU OF RECLAMATION